Регулятор насоса для твердотопливных котлов RT ST-21 с дисплеем
Controllers for CH Pumps
Principle of Operation
The EU-21 regulator (with an LED display) is intended to control the CH water circulation pump. The regulator’s task is to switch the pump on when the temperature reaches the set value and to switch it off when the boiler cools down below the set hysteresis value. Such an operation mode prevents an unnecessary activation of the pump which makes it possible to save electricity, as well as extends the pump’s life and improves its reliability. The EU-21 regulator may also serve as a thermostat by switching the pump on after reaching the set temperature. The controller also has the anti-stop function which prevents the pump stagnation beyond season (the pump switches on approx. every 10 days for 1 minute). The anti-freeze function is additional protection designed to prevent water from freezing in the installation (when the temperature drops below 6°C, the pump is switched on permanently).
Functions Performed by the Controller:
Controlling the CH or DHW pump
May operate as a thermostat
Anti-stop function
Anti-freeze function
Controller’s Equipment:
CH temperature sensor
LED display
Specification | Unit | |
Power supply | V | 230V/50Hz +/-10% |
Max. power consumption | W | 2 |
Ambient temperature | °C | 5÷50 |
Max. pumps output load | A | 1 |
Temperature CH adjustment range | °C | 25÷85 |
Hysteresis | °C | 1÷10 |
Measurement accuracy | °C | 1 |
Sensor thermal resistance | °C | -25÷90 |
Fuse | A | 1,6 |
Sensor cable length | m | 1,5 |